KB-31698: Number of SQL clients required in an E3 application.

Question:

How many SQL client licenses are required in an application with two E3Servers (in Hot-Standby) and five Viewers?

Solution:

The communication between E3 and the database happens exclusively in the machine running the E3Server, which means the Viewers will not communicate directly with the database. Therefore, in an application with two E3Servers working in Hot-Standby, E3 will require two SQL clients.