BUG-0009280: Switchover from active to standby server takes longer than expected.

OVERVIEW

When the HOT server’s network cable is unplugged, the time of switchover between hot-standby servers is always higher than 20 seconds, regardless of how long this time has been set in the domain’s “switchover time” option.

HOW CAN I REPRODUCE THIS PROBLEM?

  • Execute a HotStandby domain
  • Unplug the network cable from the active (HOT) server
  • After 20 seconds, the Standby machine will execute the domain
SITUATION

Elipse Software has confirmed that this is in fact a bug from the products listed by the end of this article. The correction download for version 3.0 can be found here.THIS ARTICLE APPLIES TO THESE PRODUCTS:

Elipse E3 version 3.0 (build 432 or lower)
Elipse E3 version 3.1 (build 139 or lower)

Print Friendly, PDF & Email

Este artigo foi útil? Was this helpful?

Classificação média - Average rating 0 / 5. Count: 0