BUG-0008263: After AlarmServer deactivation, E3Alarms does not diplay any alarms anymore.

OVERVIEW

If the AlarmServer is deactivated and then reactivated in runtime, the alarms summary becomes empty and is no longer updated.

HOW CAN I REPRODUCE THIS PROBLEM?

  • Start up a domain;
  • Activate a few alarms;
  • Deactivate AlarmServer with Deactivate method;
  • Reactivate AlarmServer with Activate method;
  • Activate a few alarms.

WORKAROUND

You can get around this problem by deactivating and then reactivating all AlarmSource objects in the application.

SITUATION

Elipse Software has confirmed that this is in fact a bug from the products listed by the end of this article. The correction download can be found here.