Question:
How can I fix the communication issues of user-generated tags in Elipse E3 or Elipse SCADA by using ABCIP and RSLogix driver with firmware v. 21?
Solution:
To do so, you must first update the driver to its latest version, because older versions of the driver don’t implement functionalities added to more recent firmwares.
Then, set up the External Access
parameter of the tag created in the device so that the Elipse E3 or Elipse SCADA will be able to both read and write in this address, according to the figure below.
parameter of the tag created in the device so that the Elipse E3 or Elipse SCADA will be able to both read and write in this address, according to the figure below.