KB-33868: Communicating with S7-200 via PPI.

Question:

How can I establish communication with an S7-200 PLC via PPI?

Solution:

To establish communication with an S7-200 PLC via PPI, you must use version 2.09 (or higher) of this driver, and configure the following items on IOKit’s Serial tab:

  • DTR: ON
  • RTS: Toggle
  • Delay Before Send: 200
  • Delay After Send: 200
  • Interbyte Delay: 100
  • InterFrame Delay: 10
These settings are necessary because an S7-200 PLC via PPI is slower than other PLCs from Siemens.
Print Friendly, PDF & Email