Question:
How can an S7-200’s VD20 be read via Ethernet with M-Prot driver?
Solution:
To establish communication with an S7-200 CP243 via Ethernet, you must set Network field as ISOTCP243. Tag’s parameters should be:
VD20 Read (uncheck the option Write on the tag)
- N1=0
- N2=709 (REAL)
- N3=1
- N4=20