{"id":359,"date":"2019-03-25T17:30:28","date_gmt":"2019-03-25T20:30:28","guid":{"rendered":"http:\/\/xexeu.elipse.com.br\/pt\/communication-between-plctp02-and-elipse-supervisory-software\/"},"modified":"2019-07-05T16:38:03","modified_gmt":"2019-07-05T19:38:03","slug":"communication-between-plctp02-and-elipse-supervisory-software","status":"publish","type":"post","link":"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/","title":{"rendered":"Communication between PLC-TP02 and Elipse Supervisory Software"},"content":{"rendered":"<p align=\"justify\"><span style=\"font-family: Tahoma;\"><strong>1) PLC Settings<\/strong><\/p>\n<p>The Programmable Logic Controller TP02 needs to be configured according to the port with which you want to perform the communication. It can either be via a MMI (RS422) port or a RS485 communication port.<\/p>\n<p>To perform the system&#8217;s memory configurations and input the instructions (Ladder) into the PLC, you need to have the program PC12 Design Center installed in your computer. This program is supplied by Weg Automation.<\/p>\n<p><strong>RS485 Communication Port<\/strong><\/p>\n<p>To perform the communication via PLC&#8217;s RS485 port, the following system memory&#8217;s configuration is required:<\/p>\n<p><strong>WS043 &#8211;\u00a0RS485 communication port function adjustment<br \/>\n<\/strong><br \/>\n0 = Computer connection<br \/>\n1 = Data connection<br \/>\n2 = Remote I\/O<\/p>\n<p><strong>WS044 &#8211; Specification of RS485 communication port adjustment<\/strong><\/p>\n<p>Table 1 \u2013 Computer&#8217;s connection:<br \/>\n<\/span><\/p>\n<table border=\"1\" width=\"100%\" cellspacing=\"2\" cellpadding=\"2\">\n<tbody>\n<tr>\n<td>\n<p align=\"center\"><strong>DATA SIZE<\/strong><\/p>\n<\/td>\n<td>\n<p align=\"center\"><strong>STOP BIT\u00a0<\/strong><\/p>\n<\/td>\n<td>\n<p align=\"center\"><strong>PARIDADE\u00a0<\/strong><\/p>\n<\/td>\n<td>\n<p align=\"center\"><strong>BAUDRATE<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">0:7 bits<\/p>\n<\/td>\n<td>\n<p align=\"center\">0:1 bit<\/p>\n<\/td>\n<td>\n<p align=\"center\">0:no<\/p>\n<\/td>\n<td>\n<p align=\"center\">0:19200<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">1:8 bits<\/p>\n<\/td>\n<td>\n<p align=\"center\">1:2 bits<\/p>\n<\/td>\n<td>\n<p align=\"center\">1:odd<\/p>\n<\/td>\n<td>\n<p align=\"center\">1:9600<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">2:even<\/p>\n<\/td>\n<td>\n<p align=\"center\">2:4800<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">3:2400<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">4:1200<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">5:600<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">6:300<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">7:38400<\/p>\n<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p><strong>WS045 &#8211;\u00a0RS485 communication port station adjustment (slave&#8217;s address on the network)<\/strong><\/p>\n<p><img loading=\"lazy\" title=\"\" src=\"http:\/\/kb.elipse.com.br\/images\/ID95\/Picture1.PNG\" alt=\"\" width=\"549\" height=\"302\" align=\"baseline\" border=\"0\" \/><br \/>\nPicture 1 \u2013 Example of setting System Memory for RS485 port<\/p>\n<p>For communication via RS485 port, you need a TP202PG cable (communication cable between the PLC and the computer), and an ADAM-4520 converser, or any other converser that converts RS232 signal into RS485 (default for RS485 port in TP02&#8217;s bornes).<\/p>\n<p>To place a second PLC onto the network you must connect one T\/R+ borne to the other in a PLC, as well as one T\/R- borne to the other, so that the PLCs communicate to each other via RS485 protocol.<\/p>\n<p><strong>RS422 MMI Communication Port<\/strong><\/p>\n<p>The communication between TP02 and Elipse software can be made via the MMI port, however this is not recommended due to its low performance and distance limitation in RS422 standards.<\/p>\n<p>For communication via PLC&#8217;s MMI port to happen, the following system memory&#8217;s configuration is required:<\/p>\n<p><strong>WS041 \u2013 MMI communication port adjustment<\/strong><\/p>\n<p>Table 2 \u2013MMI communication port<\/p>\n<table border=\"1\" width=\"100%\" cellspacing=\"2\" cellpadding=\"2\">\n<tbody>\n<tr>\n<td>\n<p align=\"center\"><strong>DATA SIZE\u00a0<\/strong><\/p>\n<\/td>\n<td>\n<p align=\"center\"><strong>STOP BIT\u00a0<\/strong><\/p>\n<\/td>\n<td>\n<p align=\"center\"><strong>PARITY\u00a0<\/strong><\/p>\n<\/td>\n<td>\n<p align=\"center\"><strong>BAUDRATE<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">0:7 bits<\/p>\n<\/td>\n<td>\n<p align=\"center\">0:1 bit<\/p>\n<\/td>\n<td>\n<p align=\"center\">0:no<\/p>\n<\/td>\n<td>\n<p align=\"center\">0:19200<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">1:8 bits<\/p>\n<\/td>\n<td>\n<p align=\"center\">1:2 bits<\/p>\n<\/td>\n<td>\n<p align=\"center\">1:odd<\/p>\n<\/td>\n<td>\n<p align=\"center\">1:9600<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">2:even<\/p>\n<\/td>\n<td>\n<p align=\"center\">2:4800<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">3:2400<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">4:1200<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">5:600<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">6:300<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<td>\n<p align=\"center\">7:38400<\/p>\n<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p><strong>WS042 &#8211; Communication port station adjustment (slave&#8217;s address on the network)<br \/>\n<\/strong><br \/>\n<img loading=\"lazy\" title=\"\" src=\"http:\/\/kb.elipse.com.br\/images\/ID95\/Picture2.PNG\" alt=\"\" width=\"550\" height=\"302\" align=\"baseline\" border=\"0\" \/><br \/>\nPicture 2 \u2013 Example of setting System Memory for MMI port<\/p>\n<p>For communication via MMI port, it is necessary that pins 4 and 5 from TP202PG cable (communication cable between the PLC and the computer) are in short circuit directly in MMI port&#8217;s connector.<\/p>\n<p><img loading=\"lazy\" title=\"\" src=\"http:\/\/kb.elipse.com.br\/images\/ID95\/Picture3.PNG\" alt=\"\" width=\"352\" height=\"325\" align=\"baseline\" border=\"0\" \/><br \/>\nPicture 3: Jumper between MMI port&#8217;s pins 4 and 5<\/p>\n<p>You will also need a TP232PG converser, which converts RS232 signal into RS422 (MMI) signal.<\/p>\n<p><img loading=\"lazy\" title=\"\" src=\"http:\/\/kb.elipse.com.br\/images\/ID95\/Picture4.PNG\" alt=\"\" width=\"395\" height=\"393\" align=\"baseline\" border=\"0\" \/><br \/>\nPicture 4: Converser TP-232PG<\/p>\n<p><strong>2) Supervisory Settings<\/p>\n<p>Driver settings [P] parameter<\/strong><\/p>\n<p>&nbsp;<\/p>\n<ul>\n<li><strong>P1<\/strong> &#8211; Serial port (10 = COM1; 20 = COM2; 30 = COM3; 40 = COM4) + data bits (0 = 7 bits; 1 = 8 bits)<\/li>\n<li><strong>P2<\/strong>\u00a0&#8211; Parity (0 = no parity; 10 = odd; 20 = even) + baud rate (0 = 19200; 1 = 9600; 2 = 4800; 3 = 2400; 4 = 1200; 5 = 600; 6 = 300; 7 = 38400)<\/li>\n<li><strong>P3 &#8211; <\/strong>Stop-bits (0 = 1-bit; 1 = 2-bits)<\/li>\n<li><strong>P4<\/strong> &#8211; Timeout (in milliseconds)<\/li>\n<\/ul>\n<p align=\"justify\">\nThe parameter P1 is defined by adding the value of serial port to the value of data bits. The parameter P2 is defined by adding the value of baud rate to the value of parity.<\/p>\n<p><strong>PLC Tags address [N] parameter<\/strong><\/p>\n<ul>\n<li><strong>N1<\/strong> &#8211;\u00a0Slave address (1 to 99) + function (see Table 3)<\/li>\n<li><strong>N2<\/strong> &#8211; Time of response (see Table 4)<\/li>\n<li><strong>N3<\/strong> &#8211; Type of register (see Table 5)<\/li>\n<li><strong>N4<\/strong> &#8211;\u00a0Register&#8217;s address (if necessary)<\/li>\n<\/ul>\n<p align=\"justify\">\nTabela 3 \u2013 Driver functions<\/p>\n<table border=\"1\" width=\"100%\" cellspacing=\"2\" cellpadding=\"2\">\n<tbody>\n<tr>\n<td>\n<p align=\"center\"><strong>VALUE\u00a0<\/strong><\/p>\n<\/td>\n<td>\n<p align=\"center\"><strong>R\/W\u00a0<\/strong><\/p>\n<\/td>\n<td>\n<p align=\"center\"><strong>FUNCTION<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">0<\/p>\n<\/td>\n<td>\n<p align=\"center\">R<\/p>\n<\/td>\n<td>\n<p align=\"center\">MCR (read only)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">0<\/p>\n<\/td>\n<td>\n<p align=\"center\">W<\/p>\n<\/td>\n<td>\n<p align=\"center\">SCS (write only)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">100<\/p>\n<\/td>\n<td>\n<p align=\"center\">R<\/p>\n<\/td>\n<td>\n<p align=\"center\">PSR (read only)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">200<\/p>\n<\/td>\n<td>\n<p align=\"center\">W<\/p>\n<\/td>\n<td>\n<p align=\"center\">STP (write only)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">300<\/p>\n<\/td>\n<td>\n<p align=\"center\">W<\/p>\n<\/td>\n<td>\n<p align=\"center\">RUN (write only)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">400<\/p>\n<\/td>\n<td>\n<p align=\"center\">W<\/p>\n<\/td>\n<td>\n<p align=\"center\">RTC (write only)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">500<\/p>\n<\/td>\n<td>\n<p align=\"center\">W<\/p>\n<\/td>\n<td>\n<p align=\"center\">WRV\u00a0(write only)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">500<\/p>\n<\/td>\n<td>\n<p align=\"center\">R<\/p>\n<\/td>\n<td>\n<p align=\"center\">MRV (read only)<\/p>\n<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Table 4 \u2013 Time of response<\/p>\n<table border=\"1\" width=\"100%\" cellspacing=\"2\" cellpadding=\"2\">\n<tbody>\n<tr>\n<td>\n<p align=\"center\"><strong>N2\u00a0<\/strong><\/p>\n<\/td>\n<td>\n<p align=\"center\"><strong>TIME(MS)<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">0<\/p>\n<\/td>\n<td>\n<p align=\"center\">0<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">1<\/p>\n<\/td>\n<td>\n<p align=\"center\">10<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">2<\/p>\n<\/td>\n<td>\n<p align=\"center\">20<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">3<\/p>\n<\/td>\n<td>\n<p align=\"center\">30<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">4<\/p>\n<\/td>\n<td>\n<p align=\"center\">40<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">5<\/p>\n<\/td>\n<td>\n<p align=\"center\">50<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">6<\/p>\n<\/td>\n<td>\n<p align=\"center\">60<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">7<\/p>\n<\/td>\n<td>\n<p align=\"center\">70<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">8<\/p>\n<\/td>\n<td>\n<p align=\"center\">80<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">9<\/p>\n<\/td>\n<td>\n<p align=\"center\">90<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">10<\/p>\n<\/td>\n<td>\n<p align=\"center\">100<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">11<\/p>\n<\/td>\n<td>\n<p align=\"center\">200<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">12<\/p>\n<\/td>\n<td>\n<p align=\"center\">300<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">13<\/p>\n<\/td>\n<td>\n<p align=\"center\">400<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">14<\/p>\n<\/td>\n<td>\n<p align=\"center\">500<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">15<\/p>\n<\/td>\n<td>\n<p align=\"center\">600<\/p>\n<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Table 5 \u2013 Register Types (N3 parameter)<\/p>\n<table border=\"1\" width=\"100%\" cellspacing=\"2\" cellpadding=\"2\">\n<tbody>\n<tr>\n<td>\n<p align=\"center\"><strong>VALUE\u00a0<\/strong><\/p>\n<\/td>\n<td>\n<p align=\"center\"><strong>MCR\/SCS\u00a0<\/strong><\/p>\n<\/td>\n<td>\n<p align=\"center\"><strong>WRV\/MRV\u00a0<\/strong><\/p>\n<\/td>\n<td>\n<p align=\"center\"><strong>RTC<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">0<\/p>\n<\/td>\n<td>\n<p align=\"center\">X<\/p>\n<\/td>\n<td>\n<p align=\"center\">V<\/p>\n<\/td>\n<td>\n<p align=\"center\">RTC Stop<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">1<\/p>\n<\/td>\n<td>\n<p align=\"center\">Y<\/p>\n<\/td>\n<td>\n<p align=\"center\">D<\/p>\n<\/td>\n<td>\n<p align=\"center\">RTC Run<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">2<\/p>\n<\/td>\n<td>\n<p align=\"center\">C<\/p>\n<\/td>\n<td>\n<p align=\"center\">F<\/p>\n<\/td>\n<td>\n<p align=\"center\">30 seconds of offset correction<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">3<\/p>\n<\/td>\n<td>\n<p align=\"center\">Sc<\/p>\n<\/td>\n<td>\n<p align=\"center\">WS<\/p>\n<\/td>\n<td>\n<p align=\"center\">RTC Update*<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p align=\"center\">4<\/p>\n<\/td>\n<td>\n<p align=\"center\">&#8211;<\/p>\n<\/td>\n<td>\n<p align=\"center\">WC<\/p>\n<\/td>\n<td>\n<p align=\"center\">\n<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p><strong>NOTA<\/strong>: The function RTC Update is a pre-command which allows updating the RTC (RTC update data must be sent subsequently by the user, by writing data in V1018-V1024).<\/p>\n<p><strong>PLC Block addressing [B] parameters<br \/>\n<\/strong><br \/>\n<strong>B1<\/strong> &#8211;\u00a0Slave address (1 to 99) + function (see Table 3)<br \/>\n<strong>B2<\/strong> &#8211;\u00a0Time of response (see Table 4)<br \/>\n<strong>B3<\/strong> &#8211;\u00a0Type of register (0 = V; 1 = D; 2 = F; 3 = WS; 4 = WC)<br \/>\n<strong>B4<\/strong> &#8211; Register&#8217;s address<\/p>\n<p><strong>NOTA<\/strong>: The functions available for block tags are WRV (write only) and MRV (read only), whose value is 500.<\/p>\n<p><strong>3) Related websites<\/strong><\/p>\n<p><a href=\"http:\/\/www.weg.com.br\/index.htm\">http:\/\/www.weg.com.br\/index.htm<\/a><br \/>\n<a href=\"http:\/\/www.elipse.com.br\">http:\/\/www.elipse.com.br<\/a><\/p>\n<p>&nbsp;<\/p>\n","protected":false},"excerpt":{"rendered":"<p>1) PLC Settings The Programmable Logic Controller TP02 needs to be configured according to the port with which you want to perform the communication. It can either be via a&hellip;<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_exactmetrics_skip_tracking":false,"_exactmetrics_sitenote_active":false,"_exactmetrics_sitenote_note":"","_exactmetrics_sitenote_category":0},"categories":[753],"tags":[],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v19.8 - https:\/\/yoast.com\/wordpress\/plugins\/seo\/ -->\n<title>Communication between PLC-TP02 and Elipse Supervisory Software - Elipse Knowledgebase<\/title>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/\" \/>\n<meta property=\"og:locale\" content=\"en_US\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Communication between PLC-TP02 and Elipse Supervisory Software\" \/>\n<meta property=\"og:description\" content=\"1) PLC Settings The Programmable Logic Controller TP02 needs to be configured according to the port with which you want to perform the communication. It can either be via a&hellip;\" \/>\n<meta property=\"og:url\" content=\"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/\" \/>\n<meta property=\"og:site_name\" content=\"Elipse Knowledgebase\" \/>\n<meta property=\"article:publisher\" content=\"http:\/\/www.facebook.com\/elipsesoftware\" \/>\n<meta property=\"article:published_time\" content=\"2019-03-25T20:30:28+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2019-07-05T19:38:03+00:00\" \/>\n<meta property=\"og:image\" content=\"http:\/\/kb.elipse.com.br\/images\/ID95\/Picture1.PNG\" \/>\n<meta name=\"author\" content=\"Elipse Software\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"Elipse Software\" \/>\n\t<meta name=\"twitter:label2\" content=\"Est. reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"3 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\/\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/#article\",\"isPartOf\":{\"@id\":\"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/\"},\"author\":{\"name\":\"Elipse Software\",\"@id\":\"https:\/\/kb.elipse.com.br\/#\/schema\/person\/def69ea453ea60b250497b89225a9f87\"},\"headline\":\"Communication between PLC-TP02 and Elipse Supervisory Software\",\"datePublished\":\"2019-03-25T20:30:28+00:00\",\"dateModified\":\"2019-07-05T19:38:03+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/\"},\"wordCount\":669,\"commentCount\":0,\"publisher\":{\"@id\":\"https:\/\/kb.elipse.com.br\/#organization\"},\"articleSection\":[\"IODriver \/ IOServer\"],\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/\",\"url\":\"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/\",\"name\":\"[:pt]Communication between PLC-TP02 and Elipse Supervisory Software[:] - Elipse Knowledgebase\",\"isPartOf\":{\"@id\":\"https:\/\/kb.elipse.com.br\/#website\"},\"datePublished\":\"2019-03-25T20:30:28+00:00\",\"dateModified\":\"2019-07-05T19:38:03+00:00\",\"breadcrumb\":{\"@id\":\"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/#breadcrumb\"},\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/\"]}]},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"In\u00edcio\",\"item\":\"https:\/\/kb.elipse.com.br\/en\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Communication between PLC-TP02 and Elipse Supervisory Software\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\/\/kb.elipse.com.br\/#website\",\"url\":\"https:\/\/kb.elipse.com.br\/\",\"name\":\"Elipse Knowledgebase\",\"description\":\"\",\"publisher\":{\"@id\":\"https:\/\/kb.elipse.com.br\/#organization\"},\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\/\/kb.elipse.com.br\/?s={search_term_string}\"},\"query-input\":\"required name=search_term_string\"}],\"inLanguage\":\"en-US\"},{\"@type\":\"Organization\",\"@id\":\"https:\/\/kb.elipse.com.br\/#organization\",\"name\":\"Elipse Software\",\"url\":\"https:\/\/kb.elipse.com.br\/\",\"sameAs\":[\"http:\/\/www.facebook.com\/elipsesoftware\"],\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\/\/kb.elipse.com.br\/#\/schema\/logo\/image\/\",\"url\":\"https:\/\/kb.elipse.com.br\/wp-content\/uploads\/2019\/05\/schererelipse-com-br\/logoElipse.png\",\"contentUrl\":\"https:\/\/kb.elipse.com.br\/wp-content\/uploads\/2019\/05\/schererelipse-com-br\/logoElipse.png\",\"width\":161,\"height\":58,\"caption\":\"Elipse Software\"},\"image\":{\"@id\":\"https:\/\/kb.elipse.com.br\/#\/schema\/logo\/image\/\"}},{\"@type\":\"Person\",\"@id\":\"https:\/\/kb.elipse.com.br\/#\/schema\/person\/def69ea453ea60b250497b89225a9f87\",\"name\":\"Elipse Software\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\/\/kb.elipse.com.br\/#\/schema\/person\/image\/\",\"url\":\"https:\/\/secure.gravatar.com\/avatar\/ff1f7ec38f4687b06f6851d97b3cd2d0?s=96&d=mm&r=g\",\"contentUrl\":\"https:\/\/secure.gravatar.com\/avatar\/ff1f7ec38f4687b06f6851d97b3cd2d0?s=96&d=mm&r=g\",\"caption\":\"Elipse Software\"},\"url\":\"https:\/\/kb.elipse.com.br\/en\/author\/webmasterelipse-com-br\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Communication between PLC-TP02 and Elipse Supervisory Software - Elipse Knowledgebase","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/","og_locale":"en_US","og_type":"article","og_title":"[:pt]Communication between PLC-TP02 and Elipse Supervisory Software[:] - Elipse Knowledgebase","og_description":"1) PLC Settings The Programmable Logic Controller TP02 needs to be configured according to the port with which you want to perform the communication. It can either be via a&hellip;","og_url":"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/","og_site_name":"Elipse Knowledgebase","article_publisher":"http:\/\/www.facebook.com\/elipsesoftware","article_published_time":"2019-03-25T20:30:28+00:00","article_modified_time":"2019-07-05T19:38:03+00:00","og_image":[{"url":"http:\/\/kb.elipse.com.br\/images\/ID95\/Picture1.PNG"}],"author":"Elipse Software","twitter_card":"summary_large_image","twitter_misc":{"Written by":"Elipse Software","Est. reading time":"3 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/#article","isPartOf":{"@id":"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/"},"author":{"name":"Elipse Software","@id":"https:\/\/kb.elipse.com.br\/#\/schema\/person\/def69ea453ea60b250497b89225a9f87"},"headline":"Communication between PLC-TP02 and Elipse Supervisory Software","datePublished":"2019-03-25T20:30:28+00:00","dateModified":"2019-07-05T19:38:03+00:00","mainEntityOfPage":{"@id":"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/"},"wordCount":669,"commentCount":0,"publisher":{"@id":"https:\/\/kb.elipse.com.br\/#organization"},"articleSection":["IODriver \/ IOServer"],"inLanguage":"en-US","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/","url":"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/","name":"[:pt]Communication between PLC-TP02 and Elipse Supervisory Software[:] - Elipse Knowledgebase","isPartOf":{"@id":"https:\/\/kb.elipse.com.br\/#website"},"datePublished":"2019-03-25T20:30:28+00:00","dateModified":"2019-07-05T19:38:03+00:00","breadcrumb":{"@id":"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/#breadcrumb"},"inLanguage":"en-US","potentialAction":[{"@type":"ReadAction","target":["https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/"]}]},{"@type":"BreadcrumbList","@id":"https:\/\/kb.elipse.com.br\/en\/communication-between-plctp02-and-elipse-supervisory-software\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"In\u00edcio","item":"https:\/\/kb.elipse.com.br\/en\/"},{"@type":"ListItem","position":2,"name":"Communication between PLC-TP02 and Elipse Supervisory Software"}]},{"@type":"WebSite","@id":"https:\/\/kb.elipse.com.br\/#website","url":"https:\/\/kb.elipse.com.br\/","name":"Elipse Knowledgebase","description":"","publisher":{"@id":"https:\/\/kb.elipse.com.br\/#organization"},"potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/kb.elipse.com.br\/?s={search_term_string}"},"query-input":"required name=search_term_string"}],"inLanguage":"en-US"},{"@type":"Organization","@id":"https:\/\/kb.elipse.com.br\/#organization","name":"Elipse Software","url":"https:\/\/kb.elipse.com.br\/","sameAs":["http:\/\/www.facebook.com\/elipsesoftware"],"logo":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/kb.elipse.com.br\/#\/schema\/logo\/image\/","url":"https:\/\/kb.elipse.com.br\/wp-content\/uploads\/2019\/05\/schererelipse-com-br\/logoElipse.png","contentUrl":"https:\/\/kb.elipse.com.br\/wp-content\/uploads\/2019\/05\/schererelipse-com-br\/logoElipse.png","width":161,"height":58,"caption":"Elipse Software"},"image":{"@id":"https:\/\/kb.elipse.com.br\/#\/schema\/logo\/image\/"}},{"@type":"Person","@id":"https:\/\/kb.elipse.com.br\/#\/schema\/person\/def69ea453ea60b250497b89225a9f87","name":"Elipse Software","image":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/kb.elipse.com.br\/#\/schema\/person\/image\/","url":"https:\/\/secure.gravatar.com\/avatar\/ff1f7ec38f4687b06f6851d97b3cd2d0?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/ff1f7ec38f4687b06f6851d97b3cd2d0?s=96&d=mm&r=g","caption":"Elipse Software"},"url":"https:\/\/kb.elipse.com.br\/en\/author\/webmasterelipse-com-br\/"}]}},"_links":{"self":[{"href":"https:\/\/kb.elipse.com.br\/en\/wp-json\/wp\/v2\/posts\/359"}],"collection":[{"href":"https:\/\/kb.elipse.com.br\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/kb.elipse.com.br\/en\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/kb.elipse.com.br\/en\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/kb.elipse.com.br\/en\/wp-json\/wp\/v2\/comments?post=359"}],"version-history":[{"count":1,"href":"https:\/\/kb.elipse.com.br\/en\/wp-json\/wp\/v2\/posts\/359\/revisions"}],"predecessor-version":[{"id":7617,"href":"https:\/\/kb.elipse.com.br\/en\/wp-json\/wp\/v2\/posts\/359\/revisions\/7617"}],"wp:attachment":[{"href":"https:\/\/kb.elipse.com.br\/en\/wp-json\/wp\/v2\/media?parent=359"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/kb.elipse.com.br\/en\/wp-json\/wp\/v2\/categories?post=359"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/kb.elipse.com.br\/en\/wp-json\/wp\/v2\/tags?post=359"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}